Total Losses in Power Distribution & Transmission Lines-Part 1
Introduction:
- Power generated in power stations pass
through large & complex networks like transformers, overhead lines,
cables & other equipments and reaches at the end users. It is fact
that the Unit of electric energy generated by Power Station does not
match with the units distributed to the consumers. Some percentage of
the units is lost in the Distribution network. This difference in the
generated & distributed units is known as Transmission and
Distribution loss.
- Transmission and Distribution loss are the amounts that are not paid for by users.
- T&D Losses= (Energy Input to feeder(Kwh)-Billed Energy to Consumer(Kwh)) / Energy Input kwh x100
- Distribution Sector considered as the
weakest link in the entire power sector. Transmission Losses is
approximate 17% while Distribution Losses is approximate 50%.
- There are two types of Transmission and Distribution Losses
- Technical Losses
- Non Technical Losses (Commercial Losses)
(1) Technical Losses:
- The technical losses are due to energy
dissipated in the conductors, equipment used for transmission Line,
Transformer, sub- transmission Line and distribution Line and magnetic
losses in transformers.
- Technical losses are normally 22.5%, and directly depend on the network characteristics and the mode of operation.
- The major amount of losses in a power
system is in primary and secondary distribution lines. While
transmission and sub-transmission lines account for only about 30% of
the total losses. Therefore the primary and secondary distribution
systems must be properly planned to ensure within limits.
- The unexpected load increase was reflected in the increase of technical losses above the normal level
- Losses are inherent to the distribution of electricity and cannot be eliminated.
- There are two Type of Technical Losses.
(a) Permanent / Fixed Technical losses:
- Fixed losses do not vary according to
current. These losses take the form of heat and noise and occur as long
as a transformer is energized.
- Between 1/4 and 1/3 of technical losses
on distribution networks are fixed losses. Fixed losses on a network
can be influenced in the ways set out below.
- Corona Losses.
- Leakage Current Losses.
- Dielectric Losses.
- Open-circuit Losses.
- Losses caused by continuous load of measuring elements
- Losses caused by continuous load of control elements.
(b) Variable Technical losses
- Variable losses vary with the amount of
electricity distributed and are, more precisely, proportional to the
square of the current. Consequently, a 1% increase in current leads to
an increase in losses of more than 1%.
- Between 2/3 and 3/4 of technical (or physical) losses on distribution networks are variable Losses.
- By increasing the cross sectional area
of lines and cables for a given load, losses will fall. This leads to a
direct trade-off between cost of losses and cost of capital expenditure.
It has been suggested that optimal average utilization rate on a
distribution network that considers the cost of losses in its design
could be as low as 30 per cent.
- joule losses in lines in each voltage level
- impedance losses
- Losses caused by contact resistance.
Main Reasons for Technical Losses:
(1) Lengthy Distribution lines:
- In practically 11 KV and 415 volts
lines, in rural areas are extended over long distances to feed loads
scattered over large areas. Thus the primary and secondary distributions
lines in rural areas are largely radial laid usually extend over long
distances. This results in high line resistance and therefore high I2R
losses in the line.
- Haphazard growths of sub-transmission and distribution system in to new areas.
- Large scale rural electrification through long 11kV and LT lines.
(2) Inadequate Size of Conductors of Distribution lines:
- The size of the conductors should be
selected on the basis of KVA x KM capacity of standard conductor for a
required voltage regulation but rural loads are usually scattered and
generally fed by radial feeders. The conductor size of these feeders
should be adequate.
(3) Installation of Distribution transformers away from load centers:
- Distribution Transformers are not located at Load center on the Secondary Distribution System.
- In most of case Distribution
Transformers are not located centrally with respect to consumers.
Consequently, the farthest consumers obtain an extremity low voltage
even though a good voltage levels maintained at the transformers
secondary. This again leads to higher line losses. (The reason for the
line losses increasing as a result of decreased voltage at the consumers
end Therefore in order to reduce the voltage drop in the line to the
farthest consumers, the distribution transformer should be located at
the load center to keep voltage drop within permissible limits.
(4) Low Power Factor of Primary and secondary distribution system:
- In most LT distribution circuits
normally the Power Factor ranges from 0.65 to 0.75. A low Power Factor
contributes towards high distribution losses.
- For a given load, if the Power Factor
is low, the current drawn in high And the losses proportional to
square of the current will be more. Thus, line losses owing to the poor
PF can be reduced by improving the Power Factor. This can be done by
application of shunt capacitors.
- Shunt capacitors can be connected
either in secondary side (11 KV side) of the 33/11 KV power transformers
or at various point of Distribution Line.
- The optimum rating of capacitor banks
for a distribution system is 2/3rd of the average KVAR requirement of
that distribution system.
- The vantage point is at 2/3rd the length of the main distributor from the transformer.
- A more appropriate manner of improving
this PF of the distribution system and thereby reduce the line losses is
to connect capacitors across the terminals of the consumers having
inductive loads.
- By connecting the capacitors across
individual loads, the line loss is reduced from 4 to 9% depending upon
the extent of PF improvement.
(5) Bad Workmanship:
- Bad Workmanship contributes significantly role towards increasing distribution losses.
- Joints are a source of power loss.
Therefore the number of joints should be kept to a minimum. Proper
jointing techniques should be used to ensure firm connections.
- Connections to the transformer
bushing-stem, drop out fuse, isolator, and LT switch etc. should be
periodically inspected and proper pressure maintained to avoid sparking
and heating of contacts.
- Replacement of deteriorated wires and services should also be made timely to avoid any cause of leaking and loss of power.
(6) Feeder Phase Current and Load Balancing:
- One of the easiest loss savings of the distribution system is balancing current along three-phase circuits.
- Feeder phase balancing also tends to
balance voltage drop among phases giving three-phase customers less
voltage unbalance. Amperage magnitude at the substation doesn’t
guarantee load is balanced throughout the feeder length. Feeder phase
unbalance may vary during the day and with different seasons. Feeders
are usually considered “balanced” when phase current magnitudes are
within 10.Similarly, balancing load among distribution feeders will also
lower losses assuming similar conductor resistance. This may require
installing additional switches between feeders to allow for appropriate
load transfer.
- Bifurcation of feeders according to Voltage regulation and Load.
(7) Load Factor Effect on Losses:
- Power consumption of Customer varies
throughout the day and over seasons. Residential customers generally
draw their highest power demand in the evening hours. Same commercial
customer load generally peak in the early afternoon. Because current
level (hence, load) is the primary driver in distribution power losses,
keeping power consumption more level throughout the day will lower peak
power loss and overall energy losses. Load variation is Called load
factor and It varies from 0 to 1.
- Load Factor=Average load in a specified time period / peak load during that time period.
- For example, for 30 days month (720
hours) peak Load of the feeder is 10 MW. If the feeder supplied a total
energy of 5,000 MWH, the load factor for that month is (5,000 MWh)/
(10MW x 720) =0.69.
- Lower power and energy losses are
reduced by raising the load factor, which, evens out feeder demand
variation throughout the feeder.
- The load factor has been increase by
offering customers “time-of-use” rates. Companies use pricing power to
influence consumers to shift electric-intensive activities during
off-peak times (such as, electric water and space heating, air
conditioning, irrigating, and pool filter pumping).
- With financial incentives, some
electric customers are also allowing utilities to interrupt large
electric loads remotely through radio frequency or power line carrier
during periods of peak use. Utilities can try to design in higher load
factors by running the same feeders through residential and commercial
areas
(8) Transformer Sizing and Selection:
- Distribution transformers use copper
conductor windings to induce a magnetic field into a grain-oriented
silicon steel core. Therefore, transformers have both load losses and
no-load core losses.
- Transformer copper losses vary with load based on the resistive power loss equation (P loss = I2R).
- For some utilities, economic
transformer loading means loading distribution transformers to
capacity-or slightly above capacity for a short time-in an effort to
minimize capital costs and still maintain long transformer life.
- However, since peak generation is
usually the most expensive, total cost of ownership (TCO) studies should
take into account the cost of peak transformer losses. Increasing
distribution transformer capacity during peak by one size will often
result in lower total peak power dissipation-more so if it is over
Loaded.
- Transformer no-load excitation
loss(iron loss) occurs from a changing magnetic field in the transformer
core whenever it is energized. Core loss varies slightly with voltage
but is essentially considered constant. Fixed iron loss depends on
transformer core design and steel lamination molecular structure.
Improved manufacturing of steel cores and introducing amorphous metals
(such as metallic glass) have reduced core losses.
(9) Balancing 3 phase loads
- Balancing 3-phase loads periodically
throughout a network can reduce losses significantly. It can be done
relatively easily on overhead networks and consequently offers
considerable scope for Cost effective loss reduction, given suitable
incentives.
(10) Switching off transformers
- One method of reducing fixed losses is
to switch off transformers in periods of low demand. If two transformers
of a certain size are required at a substation during peak periods,
only one might be required during times of low demand so that the other
transformer might be switched off in order to reduce fixed losses.
- This will produce some offsetting
increase in variable losses and might affect security and quality of
supply as well as the operational condition of the transformer itself.
However, these trade-offs will not be explored and optimized unless the
cost of losses are taken into account.
(11) Other Reasons for Technical Losses:
- Unequal load distribution among three phases in L.T system causing high neutral currents.
- leaking and loss of power
- Over loading of lines.
- Abnormal operating conditions at which power and distribution transformers are operated
- Low voltages at consumer terminals causing higher drawl of currents by inductive loads.
- Poor quality of equipment used in
agricultural pumping in rural areas, cooler air-conditioners and
industrial loads in urban areas.
No comments:
Post a Comment